The DSE701 MKII is a compact control module that offers a range of features for single-set applications. The controller can be used in manual or auto start mode.
Original DSE701MKII | Manual & Auto Start Control Module | 0701-05
2 in stock
Limit Stock
OVERALL SIZE
72 mm x 72 mm x 38 mm (2.8” x 2.8” x 1.5”)
Excludes Key Switch
PANEL CUTOUT SIZE
68 mm x 68 mm (2.7 ” x 2.7″)
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.14kg
PRODUCT VARIANTS
0701-05 – 701MKII Manual & Auto Start Control Module
Call for Quote for international purchases!
$204.92
2 in stock
Weight | 0.9 oz |
---|---|
Dimensions | 8 × 8 × 4 in |
BRANDS | DSE |
Technical Specifications
Key Features | Key Benefits |
Front panel key switch. | Ensures the generator can only be operated when the key is used. |
Configurable for use as a manual or auto start control module. | Helps to reduce module variants held in stock. |
Auxiliary shutdown input (manual mode only). | Provides a simple input for a remote stop switch. |
LED status indication. | Provides instant generator operating status. |
Engine pre-heat. | Warms the engine to a safe temperature at start-up to increase engine life. |
Engine monitoring & protection. | Protects engine from long-term damage. |
Over speed protection. | Prevents engines running too fast and becoming damaged. |
DSE Configuration Suite Lite PC Software (DSE813 required). | Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring. |
Monitors battery charging status using the WL terminal on the charge alternator. | When the battery has a charging fault the module illuminates an LED on its front panel. |
Details
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without internal batteries.
MAXIMUM OPERATING CURRENT
26 mA at 12 V, 27 mA at 24 V
MAXIMUM STANDBY CURRENT
20 mA at 12 V, 21 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V TO 35 V
OUTPUTS
START
Solid state 1.2 A negative grounding terminal
RUN
Solid state 1.2 A negative grounding terminal
PRE-HEAT
Solid state 1.2 A negative grounding terminal
GENERATOR
VOLTAGE RANGE
15 V – 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz