Original DSE4520 MKII | Auto Mains (Utility) Failure Control Module

DSE

Limit Stock
OVERALL SIZE
140 mm x 113 mm x 43 mm (5.5” x 4.4” x 1.5”)
PANEL CUTOUT SIZE
118 mm x 92 mm (4.6″ x 3.6″)
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.26kg
PRODUCT VARIANTS
4520-05 – 4520 Auto Mains (Utility) Failure Control Module (Ct, Rtc)
4520-35 – 4520 Auto Mains (Utility) Failure Control Module (Ct, Rtc, Htr)

$489.99

KEY BENEFITS

The DSE4520 MKII is a compact Auto Mains (Utility) Failure Control Module that has been developed to provide an outstanding range of features within a compact enclosure. 

  • CAN & alternator speed sensing.
  • Largest back-lit display in its class
  • Heated display option.
  • Provides full monitoring flexibility.
  • Provides clear and easy to read information pages.
  • Ensures the display continues to operate in extreme cold weather conditions.
  • 600 V ph-ph nominal system compatibility.
  • Provides global flexibility.
  • Generator & load power monitoring (kW, kV A, kV Ar, pf).
  • Accumulated power monitoring (kW h, kVA h, kVAr h).
  • Provides clear accurate power measurement information.
  • Provides a true indication of the amount of energy the generator has provided.
  • Generator overload protection (kW).
  • Fuel and start outputs (configurable on CAN).
Weight 0.15 oz
Dimensions 8 × 8 × 4 in
BRANDS

DSE

Technical Specifications

Key Features Key Benefits
CAN & alternator speed sensing. Provides full monitoring flexibility.
Largest back-lit display in its class Provides clear and easy to read information pages.
Heated display option. Ensures the display continues to operate in extreme cold weather conditions.
Backed-up real time clock. Ensures data is not lost when module is disconnected from its power source.
Fully configurable via DSE Configuration Suite PC Software Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Power save mode. Minimises battery drain when the system is not in use.
3-phase generator and mains (utility) sensing. Provides true generator and mains (utility) sensing.
600 V ph-ph nominal system compatibility. Provides global flexibility.
Generator & load power monitoring (kW, kV A, kV Ar, pf). Provides clear accurate power measurement information.
Accumulated power monitoring (kW h, kVA h, kVAr h). Provides a true indication of the amount of energy the generator has provided.
Generator overload protection (kW). Provides engine overload protection.
Generator/load current monitoring & protection. Protects generator against overload.
Fuel and start outputs (configurable on CAN). Provides multiple installation options.

Details

DC SUPPLY

CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.

MAXIMUM OPERATING CURRENT
85 mA at 12 V, 96 mA at 24 V

MAXIMUM STANDBY CURRENT
51 mA at 12 V, 47 mA at 24 V

MAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V

MAXIMUM DEEP SLEEP CURRENT
<10 uA at 12 V, <10 uA at 24 V

OUTPUTS

OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage

OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage

AUXILIARY OUTPUTs C & D
2 A DC at supply voltage ­­

GENERATOR

VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

Open chat
1
💬Need help?
This Original DSE4520 MKII | Auto Mains (Utility) Failure Control Module can be yours for only $489.99.
If you have a question, ask us.